Radiator size calculator

A radiator rated at ΔT50 gives less with cooler water: output = rating × (ΔT / 50)^1.3. For a room that loses 1,200 W, a heat pump at 45/40 °C needs 3,595 W (12,265 BTU/h) of radiator at ΔT50; a boiler at 75/65 °C, 1,232 W. Radiators are sold by their ΔT50 output, so that is the figure to compare in a catalogue.

The room
From the heat loss calculator; 1 W = 3.412 BTU/h.
Heat pumps run 35–55 °C flow, about 5 °C drop; boilers 70–80 °C, 10–20 °C drop.
1.3 for panel radiators; the maker’s sheet gives the exact one.
—
Radiator to buy, ΔT50
— W
Mean water to room
— K
Existing radiators give
— W
Room heat loss
— BTU/h

How radiator output changes with water temperature

ΔT = (flow + return) / 2 − room output = ΔT50 rating × (ΔT / 50)^n n ≈ 1.3 (EN 442) rating needed = room heat loss × (50 / ΔT)^n

A heat pump at 45/40 °C with the room at 21 °C has a mean water temperature of 42.5 °C, so ΔT = 21.5 K, and (50 / 21.5)^1.3 = 3.00: the radiator has to be rated about 3.0 times the room’s heat loss. At 75/65 °C, ΔT = 49 K and the factor is 1.03.

Output of a radiator by flow and return temperature

Flow / returnΔT (K), room 21 °CShare of ΔT50 outputΔT50 rating for 1,000 W
75 / 65 °C49.00.971,027
70 / 60 °C44.00.851,181
60 / 50 °C34.00.611,651
55 / 45 °C29.00.492,030
50 / 45 °C26.50.442,283
45 / 40 °C21.50.332,996
40 / 35 °C16.50.244,226
35 / 30 °C11.50.156,757

Arithmetic mean ΔT, as radiator makers’ tables use, and n = 1.3. With a very small temperature difference the logarithmic mean of EN 442 gives a little less.

What this page does not do

Questions people ask

How do I calculate what size radiator I need?
Work out the room's heat loss in watts, then multiply by (50 / ΔT)^1.3, ΔT being the mean water temperature minus the room's. For 1,200 W with a boiler at 75/65 °C that is 1,232 W of radiator at ΔT50.
What size radiator do I need for a heat pump?
About 3.0 times the room's heat loss at 45/40 °C flow and return with the room at 21 °C: (50 / 21.5)^1.3 = 3.00. A room losing 1,200 W needs 3,595 W at ΔT50.
How much heat does a radiator give at a lower flow temperature?
Its ΔT50 rating × (ΔT / 50)^1.3. A 1,500 W radiator gives 501 W at 45/40 °C with the room at 21 °C, 33 % of its rating.
How many BTU is a watt?
1 W = 3.412 BTU per hour, so a 1,000 W radiator is 3,412 BTU/h.
What does ΔT50 mean on a radiator?
That the output is measured with the mean water temperature 50 K above the room, for example 75 °C flow, 65 °C return and a 20 °C room (EN 442). It is the figure radiators are sold by.