Glass · Density

Glass density and unit weight

Float and toughened glass: 2500 kg/m³ (2.5 g/cm³, 156.1 lb/ft³), the figure in EN 572-1. As a unit weight that is 24.5 kN/m³, and as a weight per area 2.5 kg per m² for every millimetre of thickness (0.232 kg, 0.512 lb per square foot per mm): 10 mm glass weighs 25 kg/m², 2.32 kg per sq ft. The glass weight calculator uses the same figure for any pane, laminated make-up or insulating unit.

Glass density in every unit

UnitSoda-lime float and toughened glass
kg/m³2500
g/cm³2.5
lb/ft³156.1
Unit weight, kN/m³24.52
Per mm of thickness, kg/m²2.5
Per mm of thickness, kN/m²0.0245

Weight by thickness, from the density

Weight per area = thickness × density. Toughened, annealed and heat-strengthened glass of the same thickness weigh the same.

Thicknesskg/m²kg per sq ftlb per sq ft
3 mm7.50.6971.536
4 mm10.00.9292.048
5 mm12.51.1612.560
6 mm15.01.3943.072
8 mm20.01.8584.096
10 mm25.02.3235.120
12 mm30.02.7876.144
15 mm37.53.4847.681
19 mm47.54.4139.729

Laminated glass

The PVB interlayer is lighter than glass, about 1070 kg/m³, so a laminated pane weighs a little more than its glass alone: 4 + 4 mm with 0.76 mm PVB is 20.81 kg/m², 6 + 6 mm with 0.76 mm PVB 30.81 kg/m², 8 + 8 mm with 1.52 mm PVB 41.63 kg/m². The laminated glass weight page lists the usual make-ups.

Where the figure comes from

EN 572-1, the European standard for soda-lime silicate building glass, gives 2500 kg/m³ for float glass, and EN 12150 (toughened) and EN 14449 (laminated) build on the same glass. Low-iron (extra-clear) float glass is the same soda-lime family and is taken at the same figure. Special glasses differ (borosilicate and some fire-resistant glasses are lighter, lead glass much heavier): use the manufacturer's data sheet for those.

Questions people ask

What is the density of glass in kg/m³?
Soda-lime silicate glass, the float glass of windows and shower screens, is 2500 kg/m³ (2.5 g/cm³), the figure EN 572-1 gives. That is 2.5 kg per square metre for every millimetre of thickness: 10 mm glass weighs 25 kg/m².
Is toughened glass denser than normal glass?
No. Toughening (tempering) heats and quenches the same float glass; the density stays at 2500 kg/m³, so a toughened pane weighs the same as an annealed one of the same size and thickness.
What is the unit weight of glass in kN/m³?
2500 kg/m³ × 9.81 m/s² = 24.5 kN/m³, the value used for the self-weight of glazing in load calculations; per millimetre of thickness that is 0.0245 kN/m², about 0.025 kN/m².